Selecting between a solid-state reduced-voltage soft starter and a pulse-width-modulated variable frequency drive (VFD) for three-phase AC induction motors on packaging conveyors, vacuum systems, and processing equipment is not only a fixed-speed versus variable-speed choice. Plant electrical engineers and OEM panel builders must verify breakaway starting torque under current limits, IEEE 519 harmonic compliance at the point of common coupling, continuous cabinet heat, and motor cable reflected-wave limits before locking the motor-control bill of materials. This guide under our automation hub compares published OEM tables and buyer verification steps that also support a complete packaging line specification, ATC spindle selection, and a packaging machinery FAT checklist.
Starting Torque Physics: How Voltage-Squared Reduction Separates Soft Starters from VFDs
According to Rockwell Automation, a Direct-On-Line (DOL) or Across-The-Line starter applies full voltage, current, and torque immediately to the motor once a start command is provided, drawing approximately 6x FLA with 100% starting torque and 180% peak torque on a typical NEMA Design B or IEC Class N motor. According to Rockwell Automation, a soft starter uses an algorithm controlling three pairs of back-to-back SCRs to start and stop the motor by changing the firing angle every half cycle to control AC voltage. According to Rockwell Automation, because motor starting torque is approximately proportional to the square of the applied voltage (% Torque proportional to %Voltage2), a 60% reduction in applied voltage (using 40% voltage) results in an 84% reduction in generated torque, leaving (0.4)^2 = 0.16 or 16% of Locked Rotor Torque. According to ABB, a star-delta starter reduces starting current to about one third of direct-on-line starting while reducing starting torque to about 25 percent, is not adjustable, and produces current peaks when switching from star to delta connection. In Rockwell Automation Table 1, Full Voltage starting applies 100% voltage for 100% full-load starting torque at 600% full-load rated current, while Wye-Delta starting applies 58% voltage for 33% full-load starting torque at 200% full-load rated current. In Rockwell Automation Table 1, soft start current-limit settings of 150%, 200%, 250%, and 300% full-load rated current correspond to 25%, 33%, 42%, and 50% voltage applied during start and produce only 6%, 11%, 18%, and 25% full-load starting torque respectively. In Rockwell Automation Table 1, soft start current-limit settings of 350%, 400%, and 450% full-load rated current correspond to 58%, 67%, and 75% voltage applied during start and produce 34%, 49%, and 56% full-load starting torque respectively, where 350% current limit or 34% starting torque matches a standard Wye-Delta contactor start.
| Type of start (Rockwell Automation Table 1) | % Voltage applied during start | % Full-load starting torque | % Full-load rated current |
|---|---|---|---|
| Full Voltage | 100 | 100 | 600 |
| Wye-Delta Starting | 58 | 33 | 200 |
| Soft Start @ 150% current limit | 25 | 6 | 150 |
| Soft Start @ 200% current limit | 33 | 11 | 200 |
| Soft Start @ 250% current limit | 42 | 18 | 250 |
| Soft Start @ 300% current limit | 50 | 25 | 300 |
| Soft Start @ 350% current limit | 58 | 34 | 350 |
| Soft Start @ 400% current limit | 67 | 49 | 400 |
| Soft Start @ 450% current limit | 75 | 56 | 450 |
According to Rockwell Automation, AC variable frequency drives allow motor rated torque to be accomplished from 0 to base speed without using increased or excessive current. According to Rockwell Automation, soft starters operate on a fixed frequency where full torque is available only at full voltage and never at zero speed, requiring a mechanical brake to hold a stopped incline conveyor, whereas a VFD provides 100% torque up to line frequency at base speed (above base speed, horsepower is 100% and torque decreases) and provides zero-speed holding torque.
Soft Starter Topologies: Two-Phase vs Three-Phase Control, Inside-the-Delta Sizing, and Load Exceptions
According to Rockwell Automation, Allen-Bradley SMC-3 and SMC Flex soft starters include an integrated bypass contactor, while the SMC-50 is fully solid state for harsh, dusty environments and vibration; the internal bypass is typically rated AC-1 because it never makes or breaks current, whereas an external emergency-run bypass requires an AC-3 utilization rating. According to ABB, two-phase controlled soft starters use 4 thyristors (on R and Y phases while the B-phase cable passes through without power devices), which normally creates a DC component that acts as braking, leading to reduced starting torque and high noise during starting unless eliminated by special algorithms, and inside-delta connection is not possible in 2-phase controlled soft starters. According to ABB, PSR softstarters are two-phase controlled with 3 to 105 A rated operational current (1 to 105 A selection span) at 208 to 600 V AC across 4 frame sizes for up to 100 starts per hour, PSE softstarters are two-phase controlled with 18 to 370 A rated operational current (6 to 370 A selection span) at 208 to 600 V AC across 3 frame sizes, and PSTX softstarters are three-phase controlled with 9 to 1250 A selection span (inside-delta: 2160 A) at 208 to 600/690 V AC across 6 frame sizes. According to Rockwell Automation, a six-lead motor wired inside the delta allows a smaller soft starter to be selected—for example, a 200 Hp (140 kW) motor minimally uses a 251 A soft starter when line-connected versus a 201 A unit when wired wye-delta—whereas VFDs must be sized for 3-lead line connection based on full-load motor current. In ABB’s softstarter selection guide, bow thrusters, centrifugal pumps, compressors, short conveyor belts, elevators, and escalators are normal-duty start applications, whereas centrifugal fans, long conveyor belts, crushers, mills, and stirrers are heavy-duty loads requiring selecting the next size softstarter in the series. According to ABB, softstarters derate for altitudes between 1000-4000 m (3280-13123 ft) using % of Ie = 100 - (x-1000)/150 in meters or % of FLA = 100 - (y-3280)/480 in feet, and derate for ambient temperatures of 40 to 60 °C (104 to 140 °F) by 0.8%/°C (0.44%/°F) on PSTX and PSR and by 0.6%/°C (0.33%/°F) on PSE. According to ABB, when starting multiple motors in parallel with a single soft starter, separate overload relays must be used for each motor and the soft starter must withstand the combined starting current of all motors (e.g., two 50A motors with 5x starting current require 500A = 50x2x5); when starting three 50A motors sequentially at 5x starting current with 5, 7, and 10 second start times, the total starting current is 750A (50x3x5) and the total starting time is 22 seconds. In Rockwell Automation Table 2, soft starters cannot be used (No) with permanent magnet motors, reluctance motors, or high-torque low-current applications (all supported by VFDs), and positive displacement pumps are only Possible on a soft starter after checking with the SMC E-tool estimation wizard. Separately, Rockwell’s Low-current Restrictions note that a soft starter can limit current to 200%, which also limits applied torque. According to Rockwell Automation, the Allen-Bradley SMC Flex offers two fixed slow speeds forward (7% and 15%) and two in reverse (10% and 20%), while the SMC-50 offers adjustable slow speeds from 1% to 15% of full speed (18 to 270 rpm on an 1800 rpm motor) without a reversing contactor, functional only for minutes due to SCR and motor temperature rise; VFDs offer continuous adjustable speed but require derating below 5 Hz. According to Rockwell Automation, soft starter start times up to 30 seconds are typical (with capability up to 999 seconds if system and motor thermal capabilities allow), whereas VFD acceleration times can be set up to 3600 seconds for high-inertia loads. According to Power & Motion Tech, Schneider Electric Altivar ATS130 soft motor starters are designed for simple machines from 11 kW to 55 kW and offer an alternative to direct-on-line (DOL) motor starters in the same 55 mm or 81 mm width without requiring a control panel redesign, featuring DIN-rail mounting and spring control terminals. According to Power & Motion Tech, Schneider Electric ATS430 Altivar soft starters are designed for standard industrial machines ranging from 4 kW to 400 kW and include condition-monitoring and cybersecurity features. LS ELECTRIC America specifies three soft starter series: the LV SSC Series (Economic) rated for 200 to 575 Vac and 18 to 200 A, the LV SSM Series (Standard) rated for 200 to 690 Vac and 24 to 1250 A, and the LV SSH Series (High Voltage) rated for 2.3 to 13.8 kVac and 70 to 1700 A. In Control Global, Yaskawa Electric America application engineer Scott Richardson states that soft starters and VFDs can reduce inrush currents and machine starting torque by 30% to 75% compared to across-the-line starters, while AutomationDirect product manager Joe Kimbrell states that current flow inside a motor delta is 58% of line current and that above 5 hp to 10 hp soft starters cost less than VFDs (citing a 100-hp soft starter at around $3000 versus close to $7000 for a 100-hp VFD), with Richardson identifying 200 hp to 500 hp fixed-speed pumps, fans, mixers, and centrifuges as a good fit for soft starters.

Industrial motor control cabinet layout showing a solid-state thyristor soft starter assembly with copper busbars, heatsink fins, and a bypass contactor feeding a conveyor drive motor.
Efficiency, Cabinet Thermal Load, Centrifugal Affinity Savings, and Year 3 VFD Maintenance
According to Rockwell Automation, soft starters achieve up to 99.5 to 99.9% efficiency (dropping less than 1V across an SCR) and carry running current across bypass contacts once started, whereas VFDs are typically 95 to 98% efficient (96.5 to 97.5% for a 6-pulse drive and 97.5 to 98% for an 18-pulse drive) and run inherently hotter because active IGBTs remain on. According to Rockwell Automation, a soft starter requires little maintenance beyond keeping fan vents clear and clean, whereas a VFD operating 24 hours per day has a year 3 replacement schedule covering cooling fan motors, small cooling fans, de-ionizing filter cartridges, coolant, electrolytic bus capacitors, rectifier bus capacitors, inverter snubber capacitors, gate driver power supplies, AC/DC and DC/DC power supplies, and UPS batteries. According to WEG Electric Corporation, a VFD takes facility AC power (typically 208V, 230V, 480V, 575V, 690V / 60 Hz AC), rectifies it to DC, smooths it with chokes and a DC bus, and inverts it via PWM to control AC induction motor speed according to N = 120f / p, where N is speed in rpm, f is frequency in Hz, and p is the number of motor poles. According to WEG Electric Corporation, under the centrifugal affinity laws for fans, pumps, and compressors, flow changes linearly with speed, pressure is proportional to the square of speed, and power is proportional to the cube of speed; operating a fan at 80 percent rated speed requires 80%^3 (printed as 0.83) = 51.2 percent, or approximately half the rated power. WEG Electric Corporation states that while a variable frequency drive can initially cost two to three times more than a soft starter, it can provide energy savings of up to 50 percent over the life of the equipment. According to Compressed Air Best Practices, in food packaging plants, vacuum pumps handle delicate fruits and vegetables, assist case packing, form flat-film containers, and create vacuum seals; many plants operate dozens of small point-of-use oil-lubricated vacuum pumps on form-fill-and-seal machines that expel oil mist into ambient air, so plants should exhaust those pumps outside when co-located with compressors, and some plants centralize vacuum systems away from production areas.
Harmonic Distortion and IEEE 519-2022 Compliance at the Point of Common Coupling
According to Rockwell Automation, soft starter harmonics are typically less than 10% during starting or stopping when SCRs partially conduct and drop to virtually no harmonics at full speed or in bypass condition, and Allen-Bradley soft starters allow motor cable runs up to 762 meters (2500 feet) based on cable capacitance with no special wire type required. According to TCI, standard 6-pulse VFDs draw distorted input current at odd, non-triplen integer multiples of the 60 Hz fundamental frequency (300 Hz, 420 Hz, etc.); TCI shows that a 30% current distortion (iTHD) waveform can produce 1% voltage distortion (vTHD), while a 40% iTHD line current on longer distribution cables with larger inductance can produce 5% background vTHD. According to ABB Technical Note 158 (IEEE 519-2022 Review), clauses 1.1 Scope, 1.2 Purpose, and 5.3 Current distortion limits specify that voltage and current distortion limits apply at the user point of common coupling (PCC) to the overall installation containing nonlinear loads and shall not be used for the evaluation of an individual nonlinear load; for industrial manufacturing plants fed by a dedicated service transformer, the PCC is frequently at the HV side of the transformer, whereas for commercial users on a common service transformer it is commonly at the LV side. Under IEEE 519 clauses 3.1 Definitions, 4.0 Harmonic measurements, and 5.3 Current distortion limits, maximum demand load current (IL) at the PCC is based on the sum of the 15 min or 30 min maximum-demand rms currents from each of the twelve previous months, divided by 12, harmonic measurements must be made at least up to the 50th order, total demand distortion (TDD) is expressed as a percent of maximum demand load current (whereas THD is a percent of the fundamental), and when Ifund = 100A and Iharm = 40A, Itotal = 107.70A, changing TDD from 40/100 = 40% to 40/107.7 = 37.14%. IEEE 519-1992 Table 10-2 sets low-voltage system voltage THD limits at 3% for special applications (hospitals, airports), 5% for general systems, and 10% for dedicated systems (only converters), while Table 10-3 prescribes current demand distortion limits (iTDD) at the PCC ranging from a minimum of 5% iTDD for heavily loaded power systems (Isc/IL < 20) to a maximum of 20% iTDD for lightly loaded power systems (Isc/IL > 1000). In the Rockwell Automation Harmonic Mitigation Solutions Checklist, a 6-Pulse AC Drive with a DC Link Choke has a typical current harmonic distortion (ITHD) of 30 to 45%, does not meet IEEE 519 (No), has 97% efficiency, a baseline 1.0 relative size, and a 0.75 to 0.95 total power factor. In the Rockwell Automation Harmonic Mitigation Solutions Checklist, an 18-Pulse Converter with Auto Transformer achieves 4.5 to 6% ITHD (Meets IEEE 519: Yes, 96.5% efficiency, 3.0 to 5.0 relative size, 0.90 to 0.99 power factor), a Passive Filter with 6-Pulse AC Drive achieves 5 to 8% ITHD (Meets IEEE 519: Marginal, 96.5% efficiency, 2.0 to 6.0 relative size, lower cost for <125 Hp, 0.3 to 1.0 leading power factor), and an Active Power Filter achieves 3 to 5% ITHD (Meets IEEE 519: Yes, 96% efficiency, 2.5 to 5.0 relative size, 0.90 to 0.98 power factor). In the Rockwell Automation Harmonic Mitigation Solutions Checklist, a PowerFlex 755T Drive with Active Front End achieves 3 to 5% ITHD, meets IEEE 519 (Yes) at the drive input terminals, operates at 97% efficiency, 1.5 to 2.5 relative size, and 1.0 total power factor, and is cost-effective on single-drive applications typically greater than 50 horsepower or large common DC bus systems. According to TCI, with no background voltage distortion and a balanced 3-phase source, an 18-pulse VFD rectifier can achieve 5% input current iTHD at full load, but when background vTHD reaches 5%, its input current iTHD can increase to 12%, making it ineffective at meeting strict IEEE 519 limits. According to TCI, HarmonicGuard Passive (HGP) filters achieve less than 5% iTHD down to less than 40% drive load at typical installations (and below 5% iTHD at full load with up to 5% background vTHD), whereas HarmonicGuard Active (HGA) filters inject counter-current to reduce source current iTDD to less than 5% across 10% to 100% VFD load even with 8% background vTHD. According to Test & Measurement Tips, the EMIS TPQH3411 three-phase passive harmonic filter operates at 415 volts AC and 50 hertz across power ratings from 1.1 kilowatts to 250 kilowatts, using resistors, inductors, and capacitors tuned to the third, fifth, seventh, and eleventh harmonic orders to maintain IEEE 519 compliance on VFDs in conveyors, pumps, blowers, crushers, and compressors.

Open electrical enclosure view showing a variable frequency drive installed above a copper-wound input reactor and harmonic filter bank with louvered cabinet cooling vents.
PWM Reflected Waves, Motor Insulation Corona Inception, and Maximum Cable Length Limits
Yaskawa Application Report AR.AFD.05 lists switching device turn-on times of 0.1 microseconds (printed as 0.1 ms) for 3rd-generation IGBTs, 0.25 for 1st-generation IGBTs, 0.5 to 1.0 for bipolar transistors, 15.0 to 20.0 for GTOs, and 40.0 to 100.0 for SCRs, and notes that 230 volt 3-phase motors are adequately protected from voltage overshoot failure by present insulation standards. In Yaskawa Application Report AR.AFD.05, VFD-induced motor winding failure usually occurs in the first turn as a phase-to-phase or phase-to-stator short caused by reflected wave and voltage overshoot; using the transmission-line critical length formula L = t / 0.00624 with PWM drive output rise times t of 0.1 to 0.3 microseconds (printed as .1 to .3 ms), the minimum lead distance for a surge voltage reflection to appear is 16.0 to 48.0 m (52.0 to 156 ft). According to Yaskawa Electric America, on long VFD motor leads, motor terminals can see twice the DC bus voltage (Input Voltage rms x 110% = Vmax; Vmax x 1.414 = Max DC Bus Voltage; Max DC Bus Voltage x 2 = Max Overshoot Voltage), reaching 1500 Volts peak on a typical 460 volt system with almost 80% of that voltage distributed across the first winding of the motor. According to Yaskawa Electric America, when voltage potential across motor conductors reaches the corona inception voltage (CIV), the electric field breaks down air and ionizes oxygen (O2) into reactive ozone (O3) that attacks organic insulation; Yaskawa recommends Class F insulation or higher with properly installed phase paper that remains between the coils during stator slot insertion. Yaskawa Application Report AR.AFD.05 recommends keeping baseline VFD-to-motor lead length below 150 feet or using an Inverter Duty Motor meeting NEMA Standard MG-1 (section 31.4), which requires motors rated less than 600 VRMS to withstand 1600 volts peak and rise times greater than or equal to 0.1 µs. In Yaskawa Application Report AR.AFD.05, a 3% or 5% impedance three-phase output reactor slows output pulse rise time to about 1.1 µs and reduces dV/dT to about 540 V/µs, solving approximately 75% of long-lead motor failures (while dropping 3 to 5% of output voltage at full load) and allowing motor operation to 300 feet with the reactor at the VFD output or 650 feet with the reactor at the motor input; an output dV/dT filter slows rise time to approximately 1.2 µs and allows operation up to approximately 2000 feet (and carrier frequencies greater than 8 kHz reduce audible motor noise and current harmonics). In Rockwell Automation DRIVES-IN001 Table 16, a Type A motor (no/misplaced phase paper) has a corona inception voltage (CIV) of 850 to 1000V, a Type B motor (properly placed phase paper) has a CIV of 1000 to 1200V, a 1488V inverter-rated motor meets NEMA MG 1-1998 section 31 and withstands voltage spikes of 3.1 times rated motor voltage, and a 1329 R/L motor meets or exceeds NEMA MG1 Part 31.40.4.2. Rockwell Automation DRIVES-IN001 column definitions typically treat an older non-inverter rated motor as 1000V and a newer non-inverter rated motor as 1200V. In Rockwell Automation DRIVES-IN001, Allen-Bradley motor terminators 1204-TFA1 (5 Hp and below) and 1204-TFB2 (2 to 800 Hp) allow a maximum cable length of 182.9 m (600 ft) on 400/480/600V drives (not 690V) at a required 2 kHz PWM frequency; the 1204-RWR2-09 reflected wave reduction device allows 182.9 m (600 ft) at 2 kHz and 91.4 m (300 ft) at 4 kHz on 400/480V drives (121.9 m / 400 ft at 2 kHz and 61.0 m / 200 ft at 4 kHz on 600V drives); and the 1204-RWC-17 device with common mode choke allows 365.8 m (1200 ft) at 2 kHz on 400/480/600V drives and 243.8 m (800 ft) at 4 kHz on 400/480V drives (121.9 m / 400 ft at 4 kHz on 600V drives). Rockwell Automation DRIVES-IN001 states that capacitive cable charging current spikes affect all VFDs—making drives under 2 Hp more susceptible to overload and overcurrent trips and affecting 480V drives more than 240V drives—and recommends routing no more than three drive output wires in the same conduit, reducing carrier frequency to 2 kHz, or adding a 3-phase inductor on the drive output. In the Rockwell Automation DRIVES-IN001 Table 17 example for a 400V, Frame 3, 15 kW PowerFlex 753 and 755 wall-mount drive, with No Solution (wire only) at 2 kHz carrier frequency (parameter 38) the maximum motor lead length is 7.6 m (25 ft) for a 1000V motor, 137.2 m (450 ft) for a 1200V motor, and 365.8 m (1200 ft) for a 1488V motor; increasing carrier frequency to 4 kHz reduces the No Solution limit to 7.6 m (25 ft) at 1000V, 91.4 m (300 ft) at 1200V, 152.4 m (500 ft) at 1488V, and 213.4 m (700 ft) in the fourth column, while adding a load reactor at 4 kHz increases 1000V to 18.3 m (60 ft) and restores 1488V to 365.8 m (1200 ft). In Rockwell Automation DRIVES-IN001 Table 23 for 480V PowerFlex 40 drives (0.5 to 15 Hp at 2/4 kHz), with No Solution (wire only) the maximum motor lead length is 7.6 m (25 ft) on a 1000V motor (or 12.2 m / 40 ft on 7.5 to 15 Hp with Reactor Only), 53.3 m (175 ft) on 0.5 Hp up to 182.9 m (600 ft) on 3 to 15 Hp for a 1200V motor, and 121.9 m (400 ft) on 0.5 Hp up to 365.8 m (1200 ft) on 10 to 15 Hp for a 1488V or 1600V motor. According to Compressed Air Best Practices, the ABB Baldor-Reliance V*S Master RS vector-duty motor series (available from 1/2 to 5 hp) uses a rolled-steel frame, Class H insulation, internal shaft grounding, and three thermostats (one per phase) to deliver 1000:1 constant-torque performance while exceeding NEMA MG1 Part 31 requirements for inverter-fed applications to prevent corona discharge.

Drive output wiring arrangement showing an inductor coil mounted at the cabinet base feeding shielded motor cables routed in steel conduit toward a cast-iron pump motor.
Step-by-Step Buyer Specification and FAT Verification Procedure
In Complete Packaging Line Specification on industrialmachinesfinder.com, EDL’s equipment specification example lists a 460/480 VAC, 3-phase, 60 Hz electrical supply and 90 psi compressed air as typically preferred utilities, while requiring buyers to record temperature range, humidity range, dust, washdown, IP rating, and machine-to-machine interface ownership. In ATC Spindle Selection Basics on industrialmachinesfinder.com, Colombo’s ATC spindle line spans 0.4 HP (0.3 kW) to 47 HP (35 kW) at speeds up to 40,000 RPM with four cooling constructions—RA liquid chiller (water + glycol), RC dry compressed air, RS powered fan (V230 or V24, airflow independent of spindle rpm), and RV shaft-mounted fan (airflow dependent on spindle speed so low rpm starves cooling)—and a normal front bearing support temperature band of 100 to 140°F (maximum 150°F before excess heat jams tool holders). In Packaging Machinery FAT Checklist on industrialmachinesfinder.com, PMMI’s factory acceptance test roadmaps recommend a 24 hours minimum dry-cycle window (with a 6 hours squeezed-window example) and form/fill/seal run-length examples of two-minute stress runs and no more than five minutes for quality production runs before site commissioning affirms the run in the actual operating environment.
When preparing the motor-control section of an RFQ or factory acceptance protocol, follow this verification sequence:
- Confirm breakaway torque under the planned soft-starter current limit against Rockwell Automation Table 1, or select a VFD when zero-speed holding torque is required.
- Choose two-phase versus three-phase soft-starter control and verify inside-the-delta eligibility on six-lead motors before final ampere sizing.
- Record altitude and ambient derating for the selected soft-starter family and the year 3 VFD preventive replacement items for 24-hour duty.
- Apply IEEE 519 limits only at the plant PCC, measure at least to the 50th harmonic order, and select harmonic mitigation topology from the Rockwell checklist.
- Cap VFD motor lead length using Yaskawa baseline distance rules or Rockwell PowerFlex cable tables for the exact drive family, carrier frequency, and motor CIV class.
- Schedule dry-cycle and form/fill/seal run windows from the packaging machinery FAT checklist before site commissioning.
Sources
- Rockwell Automation — When to use a Soft Starter or an AC Variable Frequency Drive white paper (October 2014)
- Rockwell Automation — Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives (June 2019)
- Rockwell Automation — Harmonic Solutions for Variable Frequency Drives (October 2018)
- Yaskawa Electric America — Application Report on Long Drive/Motor Leads (October 1, 2006)
- WEG Electric Corporation — White Paper: Choosing a Variable Frequency Drive or Soft Starter based on your application need (2016)
- ABB — Softstarters Catalog Rev E: PSR, PSE and PSTX
- ABB — Technical Journal (April 2014): Motor starting with soft starters – reduced stresses (part 2)
- ABB — Technical Note 158: IEEE 519-2022 Review (2023-01-10)
- TCI, LLC — Technical Paper: Harmonic Filters for High Background Voltage Distortion Applications (October 7, 2013)
- Test & Measurement Tips — Three-phase filter maintains IEEE 519 harmonic distortion compliance (October 7, 2025)
- Compressed Air Best Practices — ABB Baldor-Reliance Introduces V*S Master RS Motors (November 19, 2025)
- Compressed Air Best Practices — Compressed Air and Vacuum System Purity for Food Packaging (February 25, 2026)
- Power & Motion Tech — Schneider Electric Altivar ATS130 Soft Motor Starters (July 6, 2026)
- Power & Motion Tech — Schneider Electric ATS430 Altivar Soft Starters (July 27, 2026)
- Control Global — Soft Starters versus VFDs
- LS ELECTRIC America — Soft Starter vs. VFD: Choosing the Right Motor Control for Performance and Efficiency (July 15, 2025)
- Industrial Machines Finder — Complete Packaging Line Specification: Scope and Interfaces
- Industrial Machines Finder — ATC Spindle Selection Basics: Confirm the Machine Interfaces
- Industrial Machines Finder — Packaging Machinery FAT Checklist